HVAC Calculators · Calculator
Heat Pump Sizing Calculator: Cooling Load, Balance Point and Backup Heat
Size a heat pump on the cooling load first, so it dehumidifies well in summer, then check the heating side. Find the balance point, the outdoor temperature where the heat pump's output equals the house's heat loss, and cover any shortfall below it with backup heat or a cold-climate model. A 3.5-ton standard heat pump on a 45,500 BTU/h house balances near 23 °F and needs about 6 kW of backup at 5 °F.
Heat pump size and balance point
Why heat pumps are sized on the cooling load
A heat pump is an air conditioner that can run in reverse, so in summer it faces the same problem as any AC: if it is oversized it short-cycles and leaves the house clammy. ACCA Manual S therefore sizes the heat pump close to the cooling load and treats any heating shortfall as a job for supplemental heat. A modest margin above the cooling load is accepted where heating dominates, and variable-speed equipment can stretch further because it turns down at mild loads.
In cold climates the heating load is often 1.5–2 times the cooling load. Sizing to the heating load with a single-stage unit would make it badly oversized for summer. Cold-climate variable-speed models narrow the gap because they deliver close to full output at low temperatures without being large on paper.
The balance point formula
The house's heat loss rises in a straight line as the outdoor temperature falls, reaching zero at about 65 °F, the point where internal gains from people, appliances and sun cover the rest. The heat pump's output falls as it gets colder. Where the two lines cross is the thermal balance point.
House load(T) = Heat loss × (65 − T) ÷ (65 − Design)
HP capacity(T) = Cap(design) + (Rated − Cap(design)) × (T − Design) ÷ (47 − Design)
Balance point = (a × 65 − Cap(design) + b × Design) ÷ (a + b)
where a = Heat loss ÷ (65 − Design), b = (Rated − Cap(design)) ÷ (47 − Design)
Rated heating capacity at 47 °F is taken as roughly equal to the nominal cooling size (12,000 BTU/h per ton), which holds approximately for most ducted heat pumps. Capacity at the design temperature uses the retention percentage you select. Check the manufacturer's extended performance table for the exact figures of a specific model.
Worked example
A 2,000 sq ft house in a mixed climate (20 BTU/h per sq ft of cooling), a 45,500 BTU/h heat loss at a 5 °F design temperature, with a standard heat pump keeping 60% of its capacity at 5 °F:
- Cooling load = 2,000 × 20 = 40,000 BTU/h = 3.33 tons, rounded to 3.5 tons
- Rated heating ≈ 3.5 × 12,000 = 42,000 BTU/h; at 5 °F ≈ 42,000 × 0.6 = 25,200 BTU/h
- a = 45,500 ÷ 60 = 758.3; b = (42,000 − 25,200) ÷ 42 = 400
- Balance point = (758.3 × 65 − 25,200 + 400 × 5) ÷ 1,158.3 ≈ 23 °F (22.5)
- Shortfall at 5 °F = 45,500 − 25,200 = 20,300 BTU/h = 5.9 kW, so an 8 kW heat strip
Switching to a cold-climate model (90% retention) moves the balance point to about 14 °F and cuts the backup need to about 2.3 kW, which the smallest 5 kW strip covers with room to spare for defrost cycles and emergencies.
Backup heat: strips, dual fuel or nothing
- Electric heat strips sit in the air handler and come in 5, 8, 10, 15 and 20 kW sizes. Each 5 kW draws about 21 A at 240 V, so a large kit can require a bigger electrical service.
- Dual fuel pairs the heat pump with a gas or propane furnace and switches over below a set outdoor temperature. The economic changeover point depends on fuel prices; the gas vs electric heating comparison shows how to find it.
- No backup is realistic only where the design temperature is above the balance point, or with a cold-climate unit sized so its design-temperature capacity covers the load.
Thermostats should lock out strip heat above the balance point. A common setup fault is strips firing on every morning setback, which can make a heat pump cost as much to run as plain resistance heat.
Capacity and efficiency in the cold
Below about 40 °F a heat pump also spends time in defrost, and its COP falls as the temperature drops. It is still typically 2–3 at 17 °F for good equipment, and well above 1 even at 5 °F for cold-climate models. See heat pump efficiency vs temperature and the operating temperature range for details, and the HSPF2 rating for the seasonal figure on the label.
Ducted vs ductless heat pumps
The same balance-point logic applies to ductless systems, but each head serves its own zone, so sizing is done room by room with the mini-split sizing calculator. Ducted heat pumps replace a central AC and usually share an air handler that may contain the heat strips. When converting from a gas furnace and AC, the existing ducts set limits: a heat pump delivers cooler supply air than a furnace, so it needs roughly the same airflow as for cooling, about 350–450 CFM per ton. Undersized ducts can force a smaller heat pump than the load calls for, or cause noisy registers. Have the installer check static pressure and duct capacity before committing to a size.
Inputs to get right
The two inputs that move the answer most are the heat loss and the capacity retention. Get the heat loss from a Manual J or the heating BTU calculator. Get retention from the specific model's performance data at your design temperature, rather than from a brochure's headline. For the cooling side, the AC tonnage calculator accounts for insulation, sun and duct location in more detail than the simple climate factor here.
Frequently asked questions
Should I size a heat pump for heating or cooling?
For single-stage and two-stage equipment, size for cooling and add backup heat for the shortfall. Variable-speed and cold-climate models can be sized closer to the heating load without the summer humidity penalty, because they throttle down when the load is small.
What is a good balance point?
Anything below your typical winter nighttime temperature keeps backup heat use low. In much of the country a balance point between about 15 °F and 30 °F is normal for standard equipment. Cold-climate heat pumps can push it to near or below the design temperature.
How many kW of heat strips do I need?
Enough to cover the gap between the house's heat loss and the heat pump's output at the design temperature, rounded up to the next kit size. Many installers also size strips to carry most of the load on their own in case the outdoor unit fails.
Last reviewed 2026-10-28