Duct Size Calculator: Round Duct Diameter from CFM and Velocity
Divide the airflow in CFM by the design velocity in feet per minute to get the duct's cross-sectional area, then convert that area to a diameter and round up to the next standard size. At 800 FPM, a 400 CFM run needs a 10-inch round duct, which loses roughly 0.09 in. w.c. per 100 ft in smooth metal, or about 0.046 in. w.c. over a 50 ft straight run. Flex duct and duct board raise that loss by a material factor of about 1.3 to 3.
Round duct size calculator
How duct sizing by velocity works
Air moving through a duct obeys a simple relationship: flow equals area times speed. If you know how much air a room needs (see the CFM calculator) and how fast you are willing to let it travel, the duct area falls straight out. Velocity limits exist for two reasons: faster air is noisier at the register, and friction loss climbs steeply with speed, which the blower has to overcome.
Area (ft²) = CFM ÷ Velocity (FPM)
Area (in²) = Area (ft²) × 144
Diameter (in) = 2 × √(Area in² ÷ π)
Friction, metal ≈ 0.109 × CFM^1.9 ÷ D^5.02 (in. w.c. per 100 ft, D = chosen standard size)
Friction, chosen material = Friction, metal × Material factor
Pressure drop (in. w.c.) = Friction × Length (ft) ÷ 100
The friction expression is a widely used curve fit to the standard friction chart for clean, round galvanized duct, evaluated at the standard diameter you will actually install. The material factor scales it for rougher surfaces:
| Duct material | Typical friction factor |
|---|---|
| Smooth galvanized metal | 1.0 |
| Fiberglass duct board | About 1.3 |
| Flex duct, pulled fully tight | About 1.5 |
| Flex duct with the sag found in most installs | About 2–3 |
These factors are typical planning values; the true penalty for flex depends heavily on how much it is compressed and how it is supported. The pressure drop covers the straight length only. Elbows, boots and takeoffs add equivalent length, often more than the straight duct itself, so a full Manual D design adds those before dividing the available static pressure.
Worked example
A branch needs 400 CFM and you want a standard 800 FPM velocity, using smooth galvanized metal over a 50 ft straight run.
- Area = 400 ÷ 800 = 0.50 ft², or 72 in².
- Diameter = 2 × √(72 ÷ 3.1416) = 2 × 4.79 = 9.57 in.
- Round up to the next standard size: 10 in.
- Actual velocity in a 10-inch duct (78.5 in², 0.545 ft²): 400 ÷ 0.545 = 733 FPM.
- Friction rate: 0.109 × 400^1.9 ÷ 10^5.02 ≈ 0.092 in. w.c. per 100 ft, within the usual residential design range. The material factor for metal is 1.0, so it stays 0.092.
- Pressure drop over 50 ft: 0.092 × 50 ÷ 100 = 0.046 in. w.c.
Those are the results the calculator gives with its default inputs. Switch the material to flex duct with typical sag (× 2.5) and the same 10-inch run loses about 0.229 in. w.c. per 100 ft, or 0.115 in. w.c. over 50 ft, two and a half times as much. Notice that rounding up always lowers velocity and friction, which is why designers round up rather than to the nearest size.
Typical CFM by round duct size
The table gives two capacities for each common size: the airflow at a friction rate of 0.08 in. w.c. per 100 ft (a typical Manual D design value for metal duct) and the airflow at 700 FPM. Use the smaller of the two for a quiet, conservative branch.
| Round duct | CFM at 0.08 in./100 ft | CFM at 700 FPM |
|---|---|---|
| 4 in | 35 | 60 |
| 5 in | 60 | 95 |
| 6 in | 100 | 135 |
| 7 in | 145 | 185 |
| 8 in | 205 | 245 |
| 9 in | 280 | 310 |
| 10 in | 370 | 380 |
| 12 in | 600 | 550 |
| 14 in | 900 | 750 |
| 16 in | 1,290 | 975 |
| 18 in | 1,760 | 1,235 |
| 20 in | 2,320 | 1,525 |
Small ducts are limited by friction; large trunks are limited by velocity. For flex duct, step up one size from what the metal column suggests.
Recommended velocities
| Duct section | Typical design velocity |
|---|---|
| Supply branch to bedrooms, offices | 500–700 FPM |
| Supply branch, general rooms | 600–900 FPM |
| Supply trunk | 700–900 FPM |
| Return branch and return grille duct | 400–600 FPM |
| Return trunk | 600–800 FPM |
These are typical residential figures; ACCA Manual D sets maximum velocities and works from the blower's available static pressure, so the final design can differ. Return ducts are run slower because return grilles are often in living spaces where noise is noticed. Undersized returns are one of the most common faults in existing homes; see cold air return vents.
Velocity method vs friction method
The velocity method used here is quick and keeps noise in check, which makes it ideal for checking an individual run or picking a register duct. A full Manual D design uses the friction rate method: it starts with the blower's available static pressure, subtracts the losses of the coil, filter and grilles, divides what is left by the total effective length of the longest run, and sizes every duct to that friction rate. The friction output in the calculator lets you see whether a velocity-based size also lands in a sensible friction range (about 0.05–0.10 in. w.c. per 100 ft for most homes).
Rectangular trunks can be converted to an equivalent round diameter; a rectangle with the same area does not carry the same air, because its corners add friction. Long, flat ducts are the worst.
Common duct sizing mistakes
- Sizing to the collar of the register. Register boots come in fixed sizes, but the duct feeding them should be sized to the airflow.
- Kinked or sagging flex duct. A flex run with sharp bends can carry half its rated airflow.
- Ignoring the return. The supply side gets attention, while a single small return grille throttles the whole system.
- Oversized equipment, undersized ducts. A larger AC on the same ducts raises velocity and noise and often gives short cycling. Size the system with the AC tonnage calculator first.
If some rooms are always warm and others cold, measure supply temperatures and look at the duct runs before adding capacity. Balancing dampers and an extra branch usually solve more than a bigger unit.
Frequently asked questions
What size duct do I need for 100 CFM?
A 6-inch round duct is the usual choice. It carries about 100 CFM at a friction rate near 0.08 in. w.c. per 100 ft and a velocity of roughly 500 FPM.
How many CFM can a 6-inch flex duct carry?
Plan on 75–100 CFM for a straight, fully stretched run. Sagging or compressed flex can carry noticeably less; set the duct material to one of the flex options in the calculator to see how much the friction rises.
Should I round duct size up or down?
Up. A larger duct lowers velocity, noise and friction. Rounding down raises all three and costs airflow.
Does duct size affect efficiency?
Yes. Undersized ducts raise static pressure, which lowers airflow, reduces delivered capacity and makes the blower draw more power.